MDS25 | Telco Surge Protector

MDS25

 

Protects Up to 25 2-Wire or Up to 12 4-Wire Digital Stations Lines Using RJ-21X (Amphenol) Connectors (Pins 1-50, Male In / Female Out).
Applications: Digital PBX or KSU.

TECHNICAL SPECIFICATIONS

PRODUCT SPECIFICATIONS

  • Agency Approval UL 497A (Secondary)
  • Grounding Requirements Uses Electrical AC Ground
    for use with SurgeGate Series AC Base Units
    (See installation instructions for additional grounding information)
  • Recommended Grounding Impedance <0.5 0hm
  • Width/Height/Depth/Weight 4.25” / 5.87" / 1.5" / 0.81 lbs
  • Product Warranty 5 years
  • Connected Equipment Warranty Up to $50,000

SINGLE LINE SURGE PROTECTION: (TELCO)

  • Signal Perfect Circuitry Yes
  • Auto-Resetting PTCs 160 mA (8-10 Ohms)
  • Clamping Level 110V (T-R, T-G, R-G)
  • Response Time 1-5 Nanoseconds
  • Capacitance <50pF
  • Suppression Modes Metallic & Longitudinal
  • Wires Protected  25-pairs (pins 1-50)
  • Termination Type RJ-21X (Male In / Female Out)
MDS25

FEATURES

  • Auto-Resetting Technology PTC resistors open when a surge occurs, protecting your equipment, but unlike other fuses, the PTCs close again once the surge passes. Less downtime, and less service calls
  • Expandable System Protection SurgeGate Modules can be attached to one another to expand system protection as your system grows
  • 5 Year Product Warranty This surge protector shall be free of any defects in design, materials, or workmanship, or ITW Linx will repair or replace the defective product
  • $50,000 Connected Equipment
  • AVAYA approved products: 146E, 407568161
MDS25